Products
Gas Insulated Switchgear
Features
•Achieve safety through hermetically sealed SF6 gas
•Prevention from trouble expansion into individual gas section
•Equipped the pressure relief device for inner breakdown
•Achieve equipment reliability using Vacuum interrupter
•Outstanding accuracy based on digital relay and meta
•Protection from fault expansion by each gas division
Product specifications
Rated voltage | 25.8kV | |
Rated voltage | 2000A / 630A | |
Rated frequency | 60Hz | |
Rated short-time withstand current | 25kA/1sec | |
Power frequency voltage | Phase to earth | 60kV |
Open switching | 66kV | |
Lightning Impulse | Phase to earth | 150kV |
Open switching device | 165kV | |
Duty cycle | O-0.3s-CO-15s-CO | |
Rated Dry-Air pressure | 0.05Mpa | |
Minimum Dry-Air pressure | 0.03Mpa |